DC Input


SHP 125-US-21

SHP 150-US-21

SHP 165-US-21

SHP 172-US-21

SHP FLEX-US-21

Maximum power of PV array

250000 Wp

300000 Wp

330000 Wp

344000 Wp

104000 Wp to 344000 Wp

Maximum input voltage

1500 V

1500 V

1500 V

1500 V

1500 V

MPP voltage range

705 V to 1450 V

880 V to 1450 V

924 V to 1450 V

968 V to 1450 V

298 V to 1450 V

Rated input voltage

830 V

960 V

994 V

1025 V

524 V to 1025 V

Minimum input voltage

684 V

855 V

898 V

941 V

289 V to 940 V

Initial input voltage

780 V

940 V

986 V

1032 V

317 V to 1032 V

Maximum input current

180 A

180 A

180 A

180 A

180 A

Maximum short-circuit current

325 A

325 A

325 A

325 A

325 A

Maximum reverse current into the PV modules1)

0 A

0 A

0 A

0 A

0 A

Number of independent MPP trackers

1

1

1

1

1

Number of inputs

1

1

1

1

1

1) The topology prevents a reverse current from the inverter in the system