DC Input
SHP 125-US-21 | SHP 150-US-21 | SHP 165-US-21 | SHP 172-US-21 | SHP FLEX-US-21 | |
---|---|---|---|---|---|
Maximum power of PV array | 250000 Wp | 300000 Wp | 330000 Wp | 344000 Wp | 104000 Wp to 344000 Wp |
Maximum input voltage | 1500 V | 1500 V | 1500 V | 1500 V | 1500 V |
MPP voltage range | 705 V to 1450 V | 880 V to 1450 V | 924 V to 1450 V | 968 V to 1450 V | 298 V to 1450 V |
Rated input voltage | 830 V | 960 V | 994 V | 1025 V | 524 V to 1025 V |
Minimum input voltage | 684 V | 855 V | 898 V | 941 V | 289 V to 940 V |
Initial input voltage | 780 V | 940 V | 986 V | 1032 V | 317 V to 1032 V |
Maximum input current | 180 A | 180 A | 180 A | 180 A | 180 A |
Maximum short-circuit current | 325 A | 325 A | 325 A | 325 A | 325 A |
Maximum reverse current into the PV modules1) | 0 A | 0 A | 0 A | 0 A | 0 A |
Number of independent MPP trackers | 1 | 1 | 1 | 1 | 1 |
Number of inputs | 1 | 1 | 1 | 1 | 1 |
1) The topology prevents a reverse current from the inverter in the system