AC Output


SHP 125-US-21

SHP 150-US-21

SHP 165-US-21

SHP 172-US-21

SHP FLEX-US-21

Rated power at nominal AC voltage, 60 Hz

125000 W

150000 W

165000 W

172000 W

52000 W to 172000 W

Maximum apparent AC power

125000 VA

150000 VA

165000 VA

172000 VA

52000 VA to 172000 VA

Rated grid voltage

480 V

600 V

630 V

660 V

177 V to 759 V

Nominal AC voltage

480 V

600 V

630 V

660 V

200 V to 660 V

AC voltage range1)

422 V to 582 V

480 V to 690 V

504 V to 725 V

528 V to 759 V

177 V to 759 V

Nominal AC current at nominal AC voltage

151 A

145 A

151 A

151 A

151 A

Maximum output current

151 A

151 A

151 A

151 A

151 A

Total harmonic distortion (THD)

< 0.5 %

< 0.5 %

< 0.5 %

< 0.5 %

< 0.5 %

Maximum residual output current

662.8 A

662.8 A

662.8 A

662.8 A

662.8 A

Duration of the maximum residual output current

446.7 ms

446.7 ms

446.7 ms

446.7 ms

446.7 ms

Line synchronization characteristics

Method 2

Method 2

Method 2

Method 2

Method 2

Rated grid frequency

60 Hz

60 Hz

60 Hz

60 Hz

60 Hz

Operating range at AC grid frequency 60 Hz

54 Hz to 66 Hz

54 Hz to 66 Hz

54 Hz to 66 Hz

54 Hz to 66 Hz

54 Hz to 66 Hz

Operating range at AC grid frequency 50 Hz

44 Hz to 56 Hz

44 Hz to 56 Hz

44 Hz to 56 Hz

44 Hz to 56 Hz

44 Hz to 56 Hz

Limits of accuracy of voltage measurement

2% of the AC voltage

2% of the AC voltage

2% of the AC voltage

2% of the AC voltage

2% of the AC voltage

Limits of accuracy of frequency measurement

±0.1 Hz

±0.1 Hz

±0.1 Hz

±0.1 Hz

±0.1 Hz

Limits of accuracy of time measurement at nominal trip time

± 0.1 %

± 0.1 %

± 0.1 %

± 0.1 %

± 0.1 %

Limits of accuracy of current measurement

1% of the AC current

1% of the AC current

1% of the AC current

1% of the AC current

1% of the AC current

Limits of accuracy of power (active/reactive) measurement

5% of the nominal AC power

5% of the nominal AC power

5% of the nominal AC power

5% of the nominal AC power

5% of the nominal AC power

Limits of accuracy of power factor measurement

0.01

0.01

0.01

0.01

0.01

Limits of accuracy of time measurement

0.001 s

0.001 s

0.001 s

0.001 s

0.001 s

Output power at +60°C (+140°F) at minimum MPP voltage, 60 Hz

98 kW

125 kW

125 kW

131 kW

39 kW to 131 kW

Output power at +60°C (+140°F) at maximum MPP voltage, 60 Hz

96 kW

123 kW

125 kW

131 kW

39 kW to 131 kW

Power factor at rated power

1

1

1

1

1

Range of the displacement power factor (adjustable)

0.8 overexcited to 0.8 underexcited

0.8 overexcited to 0.8 underexcited

0.8 overexcited to 0.8 underexcited

0.8 overexcited to 0.8 underexcited

Wye connection with grounded neutral point

Compatible transformer-winding configuration

Wye connection with grounded neutral point

Wye connection with grounded neutral point

Wye connection with grounded neutral point

Wye connection with grounded neutral point

Wye connection with grounded neutral point

Output phases

3

3

3

3

3

Line conductor

3 grounding conductor

3 grounding conductor

3 grounding conductor

3 grounding conductor

3 grounding conductor

Overvoltage category in accordance with UL 62109

III

III

III

III

III

1) Depending on the configured country data set