Intended Use
The Sunny Highpower is a transformerless PV inverter. It converts the direct current from the PV modules into grid-compliant three-phase current and feeds it into the utility grid via a separate transformer.
The product is intended for use in commercial, industrial or business sectors.
The product is suitable for operation in a chemically active environment in accordance with IEC 60721-3-4 as per Class 4C2.
The product is suitable for indoor and outdoor use.
When used indoors, the ventilation system at the installation site must be able to dissipate the power loss that occurs.
The product must only be operated with PV modules of protection class II in accordance with IEC 61730, application class A. The PV modules must be compatible with this product.
The product may only be operated in connection with a suitable medium-voltage transformer. The low-voltage side must be configured in a star formation and the neutral point must be grounded (for information about the requirements of the medium-voltage transformer, consult the technical information "Important Requirements for Medium-Voltage Transformers" under www.SMA-Solar.com).
PV modules with a high capacity to ground must only be used if the coupling capacity of all PV modules does not exceed 32 μF.
All components must remain within their permitted operating ranges and their installation requirements at all times.
Use SMA products only in accordance with the information provided in the enclosed documentation and with the locally applicable laws, regulations, standards and directives. Any other application may cause personal injury or property damage.
Alterations to SMA products, e.g., changes or modifications, are only permitted with the express written permission of and according to the instructions from SMA Solar Technology AG. Unauthorized alterations can be dangerous and lead to personal injury. In addition, an unauthorized alteration as well as disregard of the documentation will void guarantee and warranty claims and in most cases terminate the operating license. SMA Solar Technology AG shall not be held liable for any damage caused by such changes.
Any use of the product other than that described in the Intended Use section does not qualify as appropriate.
The documentation supplied is an integral part of SMA products. Keep the documentation in a convenient, dry place for future reference and observe all instructions contained therein.
This document does not replace any regional, state, provincial, federal or national laws, regulations or standards that apply to the installation, electrical safety and use of the product. SMA Solar Technology AG assumes no responsibility for the compliance or non-compliance with such laws or codes in connection with the installation of the product.
The type label must remain permanently attached to the product.