Technical Data
AC connection
Rated power at 230 V, 50 Hz | 2500 W |
Maximum apparent AC power at cos φ = 1 | 2500 VA |
Rated grid voltage | 230 V |
Nominal AC voltage | 220 V / 230 V / 240 V |
AC voltage range* | 180 V to 280 V |
Nominal AC current at 220 V | 11 A |
Nominal AC current at 230 V | 11 A |
Nominal AC current at 240 V | 10.5 A |
Maximum AC current | 11 A |
Total harmonic distortion of the AC current at total harmonic distortion of the AC voltage < 2%, and the AC power > 50% of the rated power | ≤3 % |
Maximum output current under fault conditions | 19 A |
Inrush current | < 20% of the nominal AC current for a maximum of 10 ms |
Rated power frequency | 50 Hz |
AC power frequency* | 50 Hz / 60 Hz |
Operating range at AC power frequency 50 Hz | 45 Hz to 55 Hz |
Operating range at AC power frequency 60 Hz | 55 Hz to 65 Hz |
Power factor at rated power | 1 |
Displacement power factor cos φ, adjustable | 0.8 overexcited to 1 to 0.8 underexcited |
Feed-in phases | 1 |
Phase connection | 1 |
Surge category in accordance with IEC 60664-1 | III |
* Depending on the configured country data set
Battery DC Input
Maximum DC power at cos φ = 1 | 2650 W |
Maximum DC voltage | 500 V |
Voltage range | 100 V to 500 V |
DC rated voltage | 360 V |
Minimum DC voltage | 100 V |
DC start voltage | 100 V |
Maximum DC current | 10 A |
Maximum short-circuit current | 18 A |
Battery type* | Li-ion |
Surge category in accordance with IEC 60664-1 | III |
* Only use batteries approved by SMA Solar Technology AG (see list of approved batteries at www.SMA-Solar.com)
Protective Devices
DC reverse polarity protection | Not available |
Input-side disconnection point | Not available |
AC short-circuit current capability | Current control |
Ground fault monitoring | Available |
Grid monitoring | SMA Grid Guard 10.0 |
Maximum permissible fuse protection | 16 A |
All-pole sensitive residual-current monitoring unit | Available |
General Data
Width x height x depth with connection cap | 450 mm x 357 mm x 122 mm |
Weight | 9.2 kg |
Length x width x height of the packaging | 597 mm x 399 mm x 238 mm |
Weight including packaging | 11.5 kg |
Climatic category in accordance with IEC 60721-3-4 | 4K4H |
Environmental category | Outdoors |
Pollution degree outside the inverter | 3 |
Pollution degree inside the inverter | 2 |
Operating temperature range | -40°C to +60°C |
Maximum permissible value for relative humidity (condensing) | 100 % |
Maximum operating altitude above MSL | 3000 m |
Noise emission, typical | < 25 dB |
Self-consumption in standby operation | < 2 W |
Self-consumption without the load necessary to supply the battery | < 10 W |
Maximum data volume per inverter with Speedwire/Webconnect | 550 MB/month |
Additional data volume when using the Sunny Portal live interface | 600 kB/hour |
WLAN range in free-field conditions | 100 m |
Quantity maximum detectable WLAN networks | 32 |
Topology | Transformerless |
Cooling method | Convection |
Degree of protection in accordance with IEC 60529 | IP65 |
Protection class in accordance with IEC 62477 | I |
Grid configurations | TN-C, TN-S, TN-CS, TT (if VN_PE < 30 V), IT, Delta IT, split phase |
Climatic Conditions
Installation in accordance with IEC 60721-3-4, Class 4K4H
Extended temperature range | -40°C to +60°C |
Extended humidity range | 0% to 100% |
Extended air pressure range | 79.5 kPa to 106 kPa |
Transport in accordance with IEC 60721-3-4, Class 2K3
Extended temperature range | -25°C to +70°C |
Equipment
DC connection | DC connector |
AC connection | Spring-cage terminal |
Battery communication | CAN bus |
Speedwire interface | As standard |
Webconnect function | As standard |
WLAN interface | As standard |
Torques
Screws for mounting | Hand-tight |
Swivel nut of the DC connector | 2 Nm |
Swivel nut of the cable gland for the AC connection. | Hand-tight |
Swivel nut cable gland network and battery communication connection | Hand-tight |
Screws for attaching the connection cap | 3.5 Nm ± 0.3 Nm |
Screw for additional grounding | 6 Nm ± 0.3 Nm |
Screws for attaching the enclosure lid | 6 Nm ± 0.3 Nm |
Data Storage Capacity
Energy yields in the course of the day | 63 days |
Daily yields | 30 years |
Event messages for users | 1000 events |
Event messages for installers | 1000 events |
Efficiency
Maximum efficiency, ηmax | 97.0 % |
European weighted efficiency, ηEU | 96.5 % |