Configuring the Active Power Mode
Qualified person
Starting the installation assistant
- Open the user interface ( > Establishing a connection to the user interface).
- Log in as Installer.
- Start the installation assistant ( > Starting the Installation Assistant).
- Select [Save and continue] after each step up until the step Grid management service.
- Make the settings as described in the following.
Setting the connected line conductors
-
In the tab Active power mode, select the line conductor to which the inverter is connected from the drop-down list Connected line conductors.
Make the settings for systems with manual setpoint
- In the tab Active power mode set the switch Grid connection point regulation to [On].
- Enter the total PV array power in the field Nominal PV system power.
- In the drop-down list Operating mode active power setting, select whether active power setting is to be performed via a fixed specification in percent or in watts.
- In the field Set active power limit, enter the value to which the active power at the grid-connection point is to be specified. The value must be set to 0 for zero power output.
Make the settings for systems with external setpoint
In the tab Active power mode set the switch Grid connection point regulation to [Off].
Activating unbalanced load limitation
Depending on the country data set, unbalanced load limitation may have already been set. In this case, check the settings.
If there are single-phase PV inverters in the system and unbalanced load limitation is requested, set Unbalanced load limitation to [On] and enter the maximum permissible unbalanced load in the field Maximum unbalanced load.
If there are three-phase PV inverters in the system, set Unbalanced load limitation to [Off].
Configuring the Active Power Mode of the PV Inverters
- Activate the PV inverter user interface.
- Log in as Installer.
- Start the installation assistant on the PV inverter user interface.
- Select [Save and continue] until the step Grid management service.
- Ensure that the function Active power setpoint is set to [On].
- In the drop-down list Operating mode active power, select the entry External setpoint.
- In the drop-down list Fallback behavior, select the entry Apply fallback values.
- In the field Fallback value of the maximum active power enter the value to which the inverter is to limit its nominal power in case of a communication failure to the higher control unit at the end of the timeout time.
- In the field Timeout, enter the time that the inverter is to wait before it limits its nominal power to the set fallback value.
- If, in the event of a 0% or 0 W specification, the inverter is not permitted to feed small amounts of active power into the utility grid, select the entry Yes in the drop-down list Grid disconnection for 0% active power setpoint. This ensures that in the event of a 0% or 0 W specification, the inverter disconnects from the utility grid and does not feed in active power.