Event Messages
Event number | Message, cause and corrective measures |
---|---|
101 102 103 105 | Grid fault The grid voltage or grid impedance at the connection point of the inverter is too high. The inverter has disconnected from the utility grid. Corrective measures:
|
202 203 205 206 | Grid fault The utility grid has been disconnected, the AC cable is damaged or the grid voltage at the connection point of the inverter is too low. The inverter has disconnected from the utility grid. Corrective measures:
|
301 | Grid fault The ten-minute average value of the grid voltage is no longer within the permissible range. The grid voltage or grid impedance at the connection point is too high. The inverter disconnects from the utility grid to maintain power quality. Corrective measures:
|
302 | Active power limit AC voltage The inverter has reduced its power due to a too-high grid voltage to ensure grid stability. Corrective measures:
|
401 404 | Grid fault The inverter has disconnected from the utility grid. A stand-alone grid or a very large change in the power frequency was detected. Corrective measures:
|
501 | Grid fault The power frequency is not within the permissible range. The inverter has disconnected from the utility grid. Corrective measures:
|
507 | Active power limit AC frequency The inverter has reduced its power due to a too-high power frequency to ensure grid stability. Corrective measures:
|
601 | Grid fault The inverter has detected an excessively high proportion of direct current in the grid current. Corrective measures:
|
701 | Frequency not permitted > Check parameter The power frequency is not within the permissible range. The inverter has disconnected from the utility grid. Corrective measures:
|
901 | No PE connection > Check connection The grounding conductor is not correctly connected. Corrective measures:
|
1001 | L / N swapped > Check connection The connection of L and N is swapped. Corrective measures:
|
1101 | Installation fault > Check connection A second line conductor is connected to N. Corrective measures:
|
1302 | Waiting for grid voltage > Installation failure grid connection > Check grid and fuses L or N not connected. Corrective measures:
|
1501 | Reconnection fault grid The changed country data set or the value of a parameter you have set does not correspond to the local requirements. The inverter cannot connect to the utility grid. Corrective measures:
|
3301 | Unstable operation There is not enough power at the DC input of the inverter for stable operation. The inverter cannot connect to the utility grid. Corrective measures:
|
3401 | DC overvoltage > Disconnect generator Overvoltage at the DC input. This can destroy the inverter. Corrective measures:
|
3501 | Insulation failure > Check generator The inverter has detected a ground fault on the DC side. Corrective measures:
|
3601 | High discharge curr. > Check generator The leakage current of the inverter and the battery is too high. There is a ground fault, a residual current or a malfunction. The inverter interrupts parallel grid operation immediately after exceeding a threshold. When the fault is eliminated, the inverter automatically reconnects to the utility grid. Corrective measures:
|
3701 | Residual current too high > Check generator The inverter detected a residual current due to brief grounding of the battery or the DC cabling. Corrective measures:
|
3801 | DC overcurrent > Check generator Overcurrent at the DC input. The inverter briefly interrupts feed-in operation. Corrective measures:
|
6603 6604 | Self-diagnosis > Overload The cause must be determined by the Service. Corrective measures:
|
6607 6608 | Self-diagnosis > Battery overcurrent The battery detected an overcurrent on the DC side. Corrective measures:
|
6609 6610 | Self-diagnosis > Battery overvoltage The battery has detected DC overvoltage. Corrective measures:
|
6701 6702 | Communication disturbed Error in the communication processor. The inverter is still in parallel grid operation. Corrective measures:
|
7001 7002 | Sensor fault A temperature sensor in the inverter is defective and the inverter interrupts the feed-in operation. The cause must be determined by the Service. Corrective measures:
|
7201 7202 | Data stor. not poss. Internal error. The inverter is still in parallel grid operation. Corrective measures:
|
7303 | Update main CPU failed The cause must be determined by the Service. Corrective measures:
|
7324 | Wait for update conditions The testing of the update conditions was not successful. The firmware update package is not suitable for this inverter. Corrective measures:
|
7331 | Update transport started Update file is being copied. |
7332 | Update transport successful Update file was copied successfully to the inverter's internal memory. |
7333 | Update transport failed Update file could not be copied to the inverter's internal memory. In the event of connection with the inverter via WLAN, a poor connection quality can be the cause. Corrective measures:
|
7337 | Update BMS failed The firmware of the battery could not be updated. Corrective measures:
|
7341 | Update Bootloader The inverter is performing a bootloader update. |
7342 | Update Bootloader failed The bootloader update failed. Corrective measures:
|
7347 | Incompatible file The configuration file is not suitable for this inverter. Corrective measures:
|
7348 | Incorrect file format The configuration file is not of the required format or is damaged. Corrective measures:
|
7349 | Incorrect login rights for configuration file The user group logged in does not have the user rights necessary to be able to import a configuration. Corrective measures:
|
7350 | Transfer of a configuration file has started The configuration file is being transferred. |
7351 | Update WLAN The inverter is updating the WLAN module. |
7352 | Update of WLAN not successful The update of the WLAN module failed. Corrective measures:
|
7353 | Update time zone database The inverter is updating the time zone database. |
7354 | Update of time zone database not successful The update of the time zone database failed. Corrective measures:
|
7355 | Update WebUI The inverter is updating the inverter user interface. |
7356 | Update of the WebUI not successful The update of the inverter user interface failed. Corrective measures:
|
7701 | Grid disconnection point Grid relay of the inverter defective. Corrective measures:
|
7702 | Relay defect Grid relay of the inverter defective. Corrective measures:
|
7703 | 24h relay test Relay test failed. Corrective measures:
|
8003 | Active power limit Temperature The inverter has reduced its power output for more than ten minutes due to excessive temperature. Corrective measures:
|
9002 | SMA Grid Guard code invalid The SMA Grid Guard code entered is incorrect. The operating parameters are still protected and cannot be changed. Corrective measures:
|
9003 | Grid parameter locked Changes to the grid parameters are now blocked. In order to be able to make changes to the grid parameters, from now on you must log in using the SMA Grid Guard code. |
9005 | Waiting for host computer This error can have the following causes:
Corrective measures:
|
9007 | Abort self-test The self-test (Italy only) was terminated. Corrective measures:
|
9301 | New battery detected The inverter has detected a new battery. Corrective measures:
|
9303 | The service life of the battery is expiring The minimum service life defined by the battery manufacturer has been reached. Corrective measures:
|
9304 | Fault in battery connection > Check battery connection This message can have several causes:
Corrective measures:
|
9305 | Unauthorized battery system The inverter has detected an incorrect battery. Corrective measures:
|
9306 | Deviation in battery voltage Too high a deviation between the battery and DC voltage of inverter was detected. Corrective measures:
|
9307 | Battery system defective (ID [xx] The battery has detected an internal error. Corrective measures:
|
9308 | Communication fault in battery system > Check battery connection The inverter receives invalid data or no data from the battery. Corrective measures:
|
9311 | Battery cell overvoltage fault The battery has detected an overvoltage of at least one battery cell. Corrective measures:
|
9312 | Battery cell undervoltage fault The battery has detected an undervoltage of at least one battery cell. Corrective measures:
|
9313 | Low temperature fault in battery > Check installation site The lower limit of the temperature range approved by the battery manufacturer has been exceeded. Corrective measures:
|
9314 | Overtemperature fault in battery > Check installation site The upper limit of the temperature range approved by the battery manufacturer has been exceeded. Corrective measures:
|
9315 | Battery imbalancing fault The states of charge of the individual battery cells differ too much. Corrective measures:
|
9334 | Battery charging test The battery test for charging the battery was started. |
9335 | Discharge battery test The battery test for discharging the battery was started. |
9336 | Start conditions for battery test not fulfilled The battery test cannot be started since the start conditions for the battery test are not fulfilled. Corrective measures:
|
9337 | Charge battery test successful The battery test for charging the battery was carried out successfully. |
9338 | Battery discharging test successful The battery test for discharging the battery was carried out successfully. |
9339 | Battery charging test failed The battery test for charging the battery was not carried out successfully. The power required in the test was not reached. The battery or the inverter limited the power due to normative requirements. Corrective measures:
|
9340 | Battery discharging test failed The battery test for discharging the battery was not carried out successfully. Corrective measures:
|
9345 | Battery charging for start process too low The state of charge of the battery is too low for the start process. The inverter can no longer charge the battery by itself. The battery must be charged immediately by a qualified person. This message causes a permanent operation inhibition, which must be reset manually. Corrective measures:
|
9347 | Battery is reporting event The battery has detected an internal error. Corrective measures:
|
10100 | Parameter [xx] set successfully. [xx] to [xx] The displayed parameter was successfully changed. |
10101 | Setting of parameter [xx] failed. [xx] to [xx] The displayed parameter was not changed. Corrective measures:
|
10102 | Parameter [xx] set successfully. [xx] to [xx] The displayed parameter was successfully changed. |
10103 | Setting of parameter [xx] failed. [xx] to [xx] The displayed parameter was not changed. Corrective measures:
|
10110 | Time synchronization failed: [x] No time information could be called up from the set NTP server. Corrective measures:
|
10118 | Parameter upload complete The configuration file was loaded successfully. |
10248 10249 | Load reduced through device reduction or increase of query interval The network is busy. Data exchange between the devices is not at an optimum and is greatly delayed. Corrective measures:
|
10250 | [Interface]: package error rate [ok / high] The package error rate has changed. If the package error rate is high, the network is overloaded or the connection to the network switch or DHCP server (router) is disturbed. Corrective measures if the package error rate is high:
|
10251 | [Interface]: communication status goes to [OK / Warning / Error / Not connected] The communication status to the network switch or DHCP server (router) has changed. An additional error message may be displayed. |
10252 | [Interface]: communication disrupted There is no valid signal on the network line. Corrective measures:
|
10253 | [Interface]: connection speed goes to [100 Mbit / 10 Mbit] The data transfer rate has changed. The cause for the status [10 Mbit] can be a defective plug, a defective cable or the pulling or plugging of the network connector. Corrective measures if the status is [10 Mbit]:
|
10254 | [Interface]: duplex mode goes to [Full / Half] The duplex mode (data transfer mode) has changed. The cause for the status [Half] can be a defective plug, a defective cable or the pulling or plugging of the network connector. Corrective measures if the status is [Half]:
|
10255 | [Interface]: Network load OK The network load has returned to a normal range after being busy. |
10282 | [User group]-Login via [protocol] locked After several incorrect login attempts, login has been blocked for a limited time. In this case, the User login will be blocked for 15 minutes, the Grid Guard login for 12 hours. Corrective measures:
|
10283 | WLAN module faulty The WLAN module integrated in the inverter is defective. Corrective measures:
|
10284 | No WLAN connection possible The inverter does not currently have a WLAN connection to the selected network. Corrective measures:
|
10285 | WLAN connection established Connection to the selected WLAN network has been established. |
10286 | WLAN connection lost The inverter has lost WLAN connection to the selected network. Corrective measures:
|
10339 | Webconnect enabled The inverter can communicate with Sunny Portal without an additional SMA communications product (e.g. Sunny Home Manager). |
10340 | Webconnect disabled The Webconnect function has been switched off. This means that the inverter can not communicate with Sunny Portal without an additional SMA communications product (e.g. Sunny Home Manager).
|
10420 | Internal consumption control was started The battery is automatically charged or discharged depending on the purchased electricity or the grid feed-in. |
10421 | Internal consumption control was stopped The automatic charging or discharging of the battery stopped due to an external control command. |
10422 | Only charging operation in internal consumption mode The battery is charged only when increased self-consumption is active. The battery is only charged again once there is sufficient PV power in the system. |
10425 | The device switches off The battery is switched off in order to protect against deep discharge. The inverter can only be recommissioned once it has been disconnected from the utility grid. |
10517 | Dynamic active power limitation started. The inverter limits the active power of the PV inverters to the set limit. |
10518 | Dynamic active power limitation terminated. The inverter terminated the active power limitation of the PV inverters. |
10520 | Supplied power: [xx] W (permitted value: [xx] W) The set active power limitation cannot be met. Corrective measures:
|
10521 | Active power was limited today for [xx] minutes. The active power limitation of the PV inverters was limited for the specified time. |
27103 | Set parameter The parameter change has been adopted. |
27104 | Parameters set successfully The parameter changes were successfully adopted. |
27107 | Update file OK The update file is suitable for this inverter and its components and is fully available for the next update step. |
27301 | Update communication The inverter is updating the communication component. |
27302 | Update main CPU The inverter is updating the inverter component. |
27312 | Update completed The inverter has successfully completed the update. |
27336 | Battery management system The inverter is updating the battery. |
29001 | Installer code valid The entered Grid Guard code is valid. Protected parameters have now been unlocked and you can adjust the parameters. The parameters will be automatically locked again after ten feed-in hours. |
29004 | Grid parameters unchanged Changing the grid parameters is not possible. |