Setting parameters for automatic backup operation


Qualified person

Procedure:

Automatic backup operation must be set in the Operation.BckTyp parameter (Configuration of the backup type) so that the automatic transfer switching device can automatically switch to automatic backup operation in the event of a grid failure.

Ensure that the parameters are set to the default values recommended by SMA Solar Technology AG Changing parameters.

Parameter

Name

Settings

Description

Operation.BckTyp

Configuration of the backup type

Off

Automatic backup operation

Backup Secure Operation

Configure the Automatic backup operation to enable the automatic transfer switching device to switch to automatic backup operation mode automatically in the event of a grid failure.

Operation.BckSwOnDl

Minimum duration of grid fault for start of automatic backup operation

0 s to 600 s

Time after a grid failure before switching to automatic backup operation.

5 s is set by default.

Operation.BckSwOffDl

Minimum duration of grid recovery for deactivation of backup operation

1 s to 600 s

Time after restoration of the AC grid before switching back to parallel grid operation.

300 s is set by default.

Operation.BckCbSwDl

Interruption of load supply during the transition from automatic backup to feed-in operation

0 s to 60 s

Time during which backup loads are not supplied while switching from automatic backup operation to parallel grid operation.

5 s is set by default.

Operation.ManRstr.IsOn

Manual restart activated

Yes

No

Select Yes to activate manual restart.

Operation.ManRstr.ManRstrBckSc

Activation of Manual Restart for reoccurring short-circuit faults in backup operation mode.

On

Off

On: The inverter remains in fault mode.

Off: In the event of a fault during automatic backup operation, the inverter repeatedly attempts to restart until the fault is cleared.

On is set by default.

To fulfill the requirements of VDE-ARE-2510, this parameter must be set to On. The parameter settings must be made differently depending on the country-specific standards.

Bck.AMaxLim

Limit for maximum continuous AC current in backup operation

Entering value in A

Maximum continuous AC current in backup operation, depending on the inverter.

Bck.Vset

Voltage in backup operation

Enter the value in volts (V)

Voltage during backup operation, depending on the inverter.