Disconnecting the Terminals from the Inverter


Qualified person

To decommission the inverter completely upon completion of its service life, proceed as described in this Section. If the inverter is defective and you have received a replacement device, observe the information on the replacement (Replacing the Product)).

Procedure:

  1. Disconnect the inverter from all voltage sources Disconnecting the Inverter from Voltage Sources).
  2. CAUTION

    Risk of burns due to hot enclosure parts.

    1. Wait 30 minutes for the enclosure to cool down.
  3. Loosen the union nut from the threaded sleeve of the AC connection and remove the cover of the AC connection area.
  4. 17145440908

  5. Unfasten the conductors L1, L2, L3, N and PE from the terminal using the screwdriver bit from the scope of delivery (tightening torque: 4 Nm).
  6. 17124632588
  7. Unscrew the swivel nut from the threaded sleeve for the network cable.
  8. 17124632716
  9. Unscrew and remove the threaded sleeve from the network port thread on the inverter.
  10. Release the connector of the network cable and pull it out of the network port on the inverter.
  11. Take the cable support sleeve out of the threaded sleeve and remove the network cable from the cable support sleeve.
  12. Lead the network cable out of the threaded sleeve and the swivel nut.
  13. 17124632844
  14. Screw the protective cap onto the network port.
  15. The same procedure applies to the BAT CAN connection as to the network connection.
  16. 17124632972
  17. Unscrew and remove the Wi-Fi antenna.
  18. If there is a protective cap available, plug the protective cap onto the jack for connecting the antenna.
  19. 17124633100
  20. If present, remove the Multi I/O connector from the socket.
  21. Put the protective cap on the socket.
  22. Remove the AC grounding conductor. To do this, unscrew the screw M5x12 at the connection point and remove the grounding cable.