Mounting the Inverter
Qualified person
Additionally required material (not included in the scope of delivery):
2 or 4 screws (depending on support surface) suitable for both the support surface and the inverter's weight
2 or 4 washers suitable for the screws
2 or 4 screw anchors (depending on support surface) suitable for the support surface and the screws
CAUTION
Risk of injury due to weight of product
Injuries may result if the product is lifted incorrectly or dropped while being transported or mounted.
- Always have two persons mount and disassemble the product.
- Wear suitable personal protective equipment for all work on the product.
Procedure:
- Align the mounting bracket using a spirit level and mark the drilling positions.
- Drill the bore holes (Ø 12 mm) at the marked areas.
- Attach the mounting bracket to the wall.
- Screw the transport handles as far as they will go into the tapped holes on the right- and left-hand side until they lie flush with the enclosure. When doing so, ensure that the carrying handles are screwed into the threaded holes so that they are perfectly straight. If the carrying handles are not screwed in straight, this can make it more difficult or even impossible to unscrew them later on and can damage the threaded holes to the extent that carrying handles can no longer be screwed into them.
- Hook the inverter into the mounting bracket.
- Remove the 2 carrying handles from the threaded holes.
- Attach the inverter to the mounting bracket using the supplied screws (M6x14, tightening torque: 3 Nm).
- Make sure that the inverter is securely attached by carefully moving the enclosure back and forth.