Event messages


Event number

Message, cause and corrective measures

101

Grid incident

The grid voltage or grid impedance at the connection point of the inverter is too high. The inverter has disconnected from the utility grid.

Corrective measures:

  • Check whether the grid voltage at the connection point of the inverter is permanently in the permissible range.

    If the grid voltage is outside the permissible range due to local grid conditions, contact the grid operator. The grid operator must agree with an adjustment of the voltage at the feed-in point or with a change of the monitored operating limits.

    If the grid voltage is permanently within the permissible range and this message is still displayed, contact the Service.

301

Grid incident

The ten-minute average value of the grid voltage is no longer within the permissible range. The grid voltage or grid impedance at the connection point is too high. The inverter disconnects from the utility grid to maintain power quality.

Corrective measures:

  • During the feed-in operation, check whether the grid voltage at the connection point of the inverter is permanently in the permissible range.

    If the grid voltage is outside the permissible range due to local grid conditions, contact the grid operator. The grid operator must agree with an adjustment of the voltage at the feed-in point or with a change of the monitored operating limits.

    If the grid voltage is permanently within the permissible range and this message is still displayed, contact the Service.

401

Grid incident

The inverter has disconnected from the utility grid. A stand-alone grid or a very large change in the grid frequency was detected.

Corrective measures:

  • Check the grid connection for significant short-term frequency fluctuations.

501

Grid incident

The power frequency is not within the permissible range. The inverter has disconnected from the utility grid.

Corrective measures:

  • If possible, check the power frequency and observe how often fluctuations occur.

    If fluctuations occur frequently and this message is displayed often, contact the grid operator and request approval to change the operating parameters of the inverter.

    If the grid operator gives his approval, discuss any changes to the operating parameters with the Service.

601

Grid incident

The inverter has detected an excessively high proportion of direct current in the grid current.

Corrective measures:

  • Check the grid connection for direct current.

  • If this message is displayed frequently, contact the grid operator and check whether the monitoring threshold on the inverter can be raised.

801

Waiting for grid voltage > Grid failure > Check AC circuit breaker

The AC cable is not correctly connected or the country data set is not correctly configured.

Corrective measures:

  • Ensure that the miniature circuit breaker is switched on.

  • Ensure that the AC cable is not damaged and that it is connected correctly.

  • Ensure that the country data set has been configured correctly.

  • Check whether the grid voltage at the connection point of the inverter is permanently in the permissible range.

    If the grid voltage is outside the permissible range due to local grid conditions, contact the grid operator. The grid operator must agree with an adjustment of the voltage at the feed-in point or with a change of the monitored operating limits.

    If the grid voltage is permanently within the permissible range and this message is still displayed, contact the Service.

901

Grounding connection missing > Check connection

The grounding conductor is not correctly connected.

Corrective measures:

  • Ensure that the grounding conductor is correctly connected.

3401

3402

3404

3407

3410

3411

3412

DC overvoltage > Disconnect PV array

Overvoltage at the DC input. This can destroy the inverter.

This message is signalized additionally by rapid flashing of the LEDs.

Corrective measures:

  • Immediately disconnect the inverter from all voltage sources.

  • Check whether the DC voltage is below the maximum input voltage of the inverter. If the DC voltage is below the maximum input voltage of the inverter, reconnect the DC connectors to the inverter.

  • If the DC voltage exceeds the maximum input voltage of the inverter, ensure that the PV array has been correctly rated or contact the installer of the PV array.

  • If this message is repeated frequently, contact Service.

3501

Insulation failure > Check generator

The inverter has detected a ground fault in the PV system.

Corrective measures:

  • Check the PV system for ground faults.

3701

Residual current too high > Check PV array

The inverter has detected a residual current through brief grounding of the PV array.

Corrective measures:

  • Check the PV system for ground faults.

3801

3802

3803

3805

3806

3807

3808

DC overcurrent > Check PV array

Overcurrent at the DC input. The inverter briefly interrupts feed-in operation.

Corrective measures:

  • If this message is displayed frequently, ensure that the PV array has been correctly rated and wired.

4301

4302

Electric arc detected

The arc-fault circuit interrupter has detected an electric arc. If the arc-fault circuit interrupter is activated using operation inhibition, the operation inhibition function must be reset manually.

6002-6412

Self-diagnosis > Device disturbance

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

6502

Self-diagnosis > Overtemperature

The inverter has switched off due to excessive temperature.

Corrective measures:

  • Clean the cooling fins on the rear of the enclosure and the air ducts on the top using a soft brush.

  • Ensure that the inverter has sufficient ventilation.

  • Ensure that the inverter is not exposed to direct solar irradiation.

6512

Minimum operating temperature not reached

The inverter will only recommence grid feed-in once the temperature has reached at least −25°C.

6603

6604

Self-diagnosis > Overload

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

6701

6702

Communication failure

Error in the communication processor, the inverter continues feeding in, however. The cause must be determined by the Service.

Corrective measures:

  • If this message is displayed frequently, contact the Service.

7102

Parameter file not found or defective

The parameter file was not found or is defective. Loading the parameter file has failed. The inverter continues to feed in.

Corrective measures:

  • Copy the parameter file to the correct folder again.

7105

Parameter setting failed

Parameters could not be set using the memory card. The inverter continues to feed in.

Corrective measures:

  • Ensure that the parameters are set correctly.

  • Ensure that you have an SMA Grid Guard code.

7106

Update file defective

The update file is defective. The update failed. The inverter continues to feed in.

7110

No update file found

No new update file was found on the SD memory card. The update failed. The inverter continues to feed in.

7112

Update file successfully copied

7113

The memory card is full or write-protected

7201

7202

Data storage not possible

7303

Host computer update failed

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

7320

The device was successfully updated

The firmware update was completed successfully.

7330

Condition test failed

The testing of the update conditions was not successful. The firmware update package is not suitable for this inverter.

7331

Update transport started

Update file is being copied.

7332

Update transport successful

Update file was copied successfully to the inverter's internal memory.

7333

Update transport failed

Update file could not be copied to the inverter's internal memory. In the event of connection with the inverter via Wi-Fi network, a poor connection quality can be the cause.

Corrective measures:

  • Retry update.

  • For Wi-Fi connection: Improve the Wi-Fi connection quality (e.g. via Wi-Fi repeater) or establish connection with the inverter via Ethernet.

  • If this message is displayed again, contact the Service.

7341

Update Bootloader

The inverter is performing a bootloader update.

7342

Update Bootloader failed

The bootloader update failed.

Corrective measures:

  • Retry update.

  • If this message is displayed again, contact the Service.

7347

Incompatible file

The configuration file is not suitable for this inverter.

Corrective measures:

  • Ensure that the selected configuration file is suitable for this inverter.

  • Retry import.

7348

Incorrect file format

The configuration file is not of the required format or is damaged.

Corrective measures:

  • Ensure that the selected configuration file is of the required format and is not damaged.

  • Retry import.

7350

Transfer of a configuration file has started

The configuration file is being transferred.

7351

Update Wi-Fi

The inverter is updating the Wi-Fi module.

7352

Update of Wi-Fi not successful

The update of the Wi-Fi module failed.

Corrective measures:

  • Retry update.

  • If this message is displayed again, contact the Service.

7353

Update time zone database

The inverter is updating the time zone database.

7354

Update of time zone database not successful

The update of the time zone database failed.

Corrective measures:

  • Retry update.

  • If this message is displayed again, contact the Service.

7355

Update WebUI

The inverter is updating the inverter user interface.

7356

Update of the WebUI not successful

The update of the inverter user interface failed.

Corrective measures:

  • Retry update.

  • If this message is displayed again, contact the Service.

7619

Communication fault with meter unit > Check communication to meter

The inverter is not receiving any data from the energy meter.

Corrective measures:

  • Ensure that the energy meter is correctly integrated into the same network as the inverter (see energy meter manual).

  • For Wi-Fi connection: Improve the Wi-Fi connection quality (e.g., via Wi-Fi repeater) or connect the inverter with the DHCP server (router) via Ethernet.

7622

No communication with the I/O module

This event is displayed during a device-internal communication error with the SMA I/O Module. The inverter will disconnect from the utility grid for safety reasons.

7702

Device fault

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

7801

Fault overvoltage protector

One or more surge arresters have tripped or one or more surge arresters are not inserted correctly.

Corrective measures:

  • Ensure that the surge arrester is inserted correctly.

  • If surge arresters have tripped, replace the tripped surge arresters with new surge arresters.

8003

Active power limit Temperature

The inverter has reduced its power output for more than 10 minutes due to excessive temperature.

Corrective measures:

  • Clean the cooling fins on the rear of the enclosure and the air ducts on the top using a soft brush.

  • Ensure that the inverter has sufficient ventilation.

  • Ensure that the ambient temperature +35°C has not been exceeded.

  • Ensure that the inverter is not exposed to direct solar irradiation.

8101

8102

8103

8104

Communication failure

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

8208

Self-test for arc fault detection: interference level too high

An error has occurred during the self-test of the arc-fault circuit interrupter. The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

8209

Self-test for arc fault detection: interference level too low

An error has occurred during the self-test of the arc-fault circuit interrupter. The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

9002

SMA Grid Guard code invalid

The SMA Grid Guard code entered is incorrect. The operating parameters are still protected and cannot be changed.

Corrective measures:

  • Enter the correct SMA Grid Guard code.

9003

Grid parameters locked

Changes to the grid parameters are now blocked. In order to be able to make changes to the grid parameters, from now on you must log in using the SMA Grid Guard code.

9005

Changing of grid parameters not possible > Ensure DC supply

This error can have the following causes:

  • The parameters to be changed are protected.

  • The DC voltage at the DC input is not sufficient to run the main CPU.

Corrective measures:

  • Enter the SMA Grid Guard code.

  • Ensure that at least the DC start voltage is available (green LED is flashing, pulsing or glowing).

9007

Abort self-test

The self-test (Italy only) was terminated.

Corrective measures:

  • Ensure that the AC connection is correct.

  • Restart the self-test.

9033

Rapid Shutdown was triggered

The inverter detected the triggering of a Rapid Shutdown. The AC side of the inverter was disconnected.

9034

Error in Rapid Shutdown System

This message can have the following causes:

  • The Rapid Shutdown Function was not correctly configured.

  • The PV array could not be correctly disconnected. Voltage can be applied to the DC inputs of the inverter.

  • The standby voltage of all PV array disconnect switches of a string is > 30 V.

Corrective measures:

  • Check the configuration of the Rapid Shutdown function and ensure that the operating mode selected is selected according to the DC disconnection unit used.

  • Check the functionality of the PV array disconnect switches.

  • Check the standby voltage of the PV array disconnect switches used and ensure that the standby voltage of all PV array disconnect switches of a string < 30 V.

9035

Rapid Shutdown successful

The voltage at the DC inputs and at the AC output of the inverter was successfully discharged.

9037

Generator connection not carried out

The PV array disconnect switches did not connect the PV generator.

Corrective measures:

  • Check the functionality of the SunSpec-compliant PV array disconnect switches.

9038

Redundant Rapid Shutdown discharge function not ensured

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

10108

Time adjusted / old time

10109

Time adjusted / new time

10110

Time synchronization failed: [xx]

No time information could be called up from the set NTP server.

Corrective measures:

  • Ensure that the NTP server was configured correctly.

  • Ensure that the inverter is integrated into a local network with Internet connection.

10118

Parameter upload complete

The configuration file was loaded successfully.

10248

[Interface]: network busy

The network is busy. Data exchange between the devices is not at an optimum and is greatly delayed.

Corrective measures:

  • Increase the query intervals.

  • If necessary, reduce the number of devices in the network.

10249

[Interface]: network overloaded

The network is overloaded. There is no data exchange between the devices.

Corrective measures:

  • Reduce the number of devices in the network.

  • If necessary, increase the data query intervals.

10250

[Interface]: package error rate [ok / high]

The package error rate has changed. If the package error rate is high, the network is overloaded or the connection to the network switch or DHCP server (router) is impaired.

Corrective measures if the package error rate is high:

  • Ensure that with an Ethernet connection, the network cable and the network connector are not damaged and that the network connectors are correctly plugged.

  • If necessary, increase the data query intervals.

  • If necessary, reduce the number of devices in the network.

10251

[Interface]: communication status goes to [OK / Warning / Error / Not connected]

The communication status to the network switch or DHCP server (router) has changed. An additional error message may be displayed.

10252

[Interface]: communication disrupted

There is no valid signal on the network line.

Corrective measures:

  • Ensure that with an Ethernet connection, the network cable and the network connector are not damaged and that the network connectors are correctly plugged.

  • Ensure that the DHCP server (router) and any network switches are signalizing correct operation.

10253

[Interface]: connection speed goes to [100 Mbit / 10 Mbit]

The data transfer rate has changed. The cause for the status [10 Mbit] can be a defective plug, a defective cable or the pulling or plugging of the network connector.

Corrective measures if the status is [10 Mbit]:

  • Ensure that with an Ethernet connection, the network cable and the network connector are not damaged and that the network connectors are correctly plugged.

  • Ensure that the DHCP server (router) and any network switches are signalizing correct operation.

10254

[Interface]: duplex mode goes to [Full / Half]

The duplex mode (data transfer mode) has changed. The cause for the status [Half] can be a defective plug, a defective cable or the pulling or plugging of the network connector.

Corrective measures if the status is [Half]:

  • Ensure that with an Ethernet connection, the network cable and the network connector are not damaged and that the network connectors are correctly plugged.

  • Ensure that the DHCP server (router) and any network switches are signalizing correct operation.

10255

[Interface]: Network load OK

The network load has returned to a normal range after being busy.

10282

[User group]-Login via [protocol] locked

After several incorrect login attempts, login has been blocked for a limited time. In this case, the User login will be blocked for 15 minutes, the Grid Guard login for 12 hours.

Corrective measures:

  • Wait until the given time has expired and then retry login.

10283

Wi-Fi module faulty

The Wi-Fi module integrated in the inverter is defective.

Corrective measures:

  • Contact the Service.

10284

No Wi-Fi connection possible

The inverter does not currently have a Wi-Fi connection to the selected network.

Corrective measures:

  • Ensure that the SSID, the Wi-Fi password and the encryption method have been entered correctly. The encryption method is specified by your Wi-Fi router or Wi-Fi access point and can be changed there.

  • Ensure that the Wi-Fi router or Wi-Fi access point is in range and is signalizing correct operation.

  • If this message is displayed often, improve the Wi-Fi connection by using a Wi-Fi repeater.

10285

Wi-Fi connection established

Connection to the selected Wi-Fi network has been established.

10286

Wi-Fi connection lost

The inverter has lost Wi-Fi connection to the selected network.

Corrective measures:

  • Ensure that the Wi-Fi router or Wi-Fi access point is still active.

  • Ensure that the Wi-Fi router or Wi-Fi access point is in range and is signalizing correct operation.

  • If this message is displayed often, improve the Wi-Fi connection by using a Wi-Fi repeater.

10339

Webconnect enabled

10340

Webconnect disabled

10431

I-V curve measurement successfully carried out

10502

Active power limit AC frequency

10513

Grid management service Fast stop: Stop by system control is executed

This event is generated by the monitoring relay of the monitoring unit when the grid and PV system protection device is triggered. The inverter disconnects from the utility grid.

10901

Start self-test |xx|

10902

Current disconnection limit for voltage increase protection |xxx| V

10903

Current disconnection limit for voltage monitoring lower maximum threshold |xxx| V

10904

Current disconnection limit for voltage monitoring upper minimum threshold |xxx| V

10905

Current disconnection limit for voltage monitoring middle minimum threshold |xxx| V

10906

Current disconnection limit for frequency monitoring switchable maximum threshold |xxx| Hz

10907

Current disconnection limit for frequency monitoring switchable minimum threshold |xxx| Hz

10908

Current disconnection limit for frequency monitoring lower maximum threshold |xxx| Hz

10909

Current disconnection limit for frequency monitoring upper minimum threshold |xxx| Hz

10910

Measured disconnection threshold for the running test point |xxx| |xx|

10911

Standard value for the running test point |xxx| |xx|

10912

Measured disconnection time for the running test point |xx| s

27103

Set parameter

The parameter changes are being adopted.

27104

Parameters set successfully

The parameter changes were successfully adopted.

27107

Update file OK

The update file found is valid.

27301

Update communication

The inverter is updating the communication component.

27302

Update main CPU

The inverter is updating the inverter component.

27312

Update completed

The inverter has successfully completed the update.

29001

Inst. code valid

The entered Grid Guard code is valid. Protected parameters have now been unlocked and you can adjust the parameters. The parameters will be automatically locked again after 10 feed-in hours.

29004

Grid parameter unchanged

Changing the grid parameters is not possible.