Event messages
Event number | Message, cause and corrective measures |
---|---|
101 | Grid incident The grid voltage or grid impedance at the connection point of the inverter is too high. The inverter has disconnected from the utility grid. Corrective measures:
|
301 | Grid incident The ten-minute average value of the grid voltage is no longer within the permissible range. The grid voltage or grid impedance at the connection point is too high. The inverter disconnects from the utility grid to maintain power quality. Corrective measures:
|
401 | Grid incident The inverter has disconnected from the utility grid. A stand-alone grid or a very large change in the grid frequency was detected. Corrective measures:
|
501 | Grid incident The power frequency is not within the permissible range. The inverter has disconnected from the utility grid. Corrective measures:
|
601 | Grid incident The inverter has detected an excessively high proportion of direct current in the grid current. Corrective measures:
|
801 | Waiting for grid voltage > Grid failure > Check AC circuit breaker The AC cable is not correctly connected or the country data set is not correctly configured. Corrective measures:
|
901 | Grounding connection missing > Check connection The grounding conductor is not correctly connected. Corrective measures:
|
3401 3402 3404 3407 3410 3411 3412 | DC overvoltage > Disconnect PV array Overvoltage at the DC input. This can destroy the inverter. This message is signalized additionally by rapid flashing of the LEDs. Corrective measures:
|
3501 | Insulation failure > Check generator The inverter has detected a ground fault in the PV system. Corrective measures:
|
3701 | Residual current too high > Check PV array The inverter has detected a residual current through brief grounding of the PV array. Corrective measures:
|
3801 3802 3803 3805 3806 3807 3808 | DC overcurrent > Check PV array Overcurrent at the DC input. The inverter briefly interrupts feed-in operation. Corrective measures:
|
4301 4302 | Electric arc detected The arc-fault circuit interrupter has detected an electric arc. If the arc-fault circuit interrupter is activated using operation inhibition, the operation inhibition function must be reset manually. |
6002-6412 | Self-diagnosis > Device disturbance The cause must be determined by the Service. Corrective measures:
|
6502 | Self-diagnosis > Overtemperature The inverter has switched off due to excessive temperature. Corrective measures:
|
6512 | Minimum operating temperature not reached The inverter will only recommence grid feed-in once the temperature has reached at least −25°C. |
6603 6604 | Self-diagnosis > Overload The cause must be determined by the Service. Corrective measures:
|
6701 6702 | Communication failure Error in the communication processor, the inverter continues feeding in, however. The cause must be determined by the Service. Corrective measures:
|
7102 | Parameter file not found or defective The parameter file was not found or is defective. Loading the parameter file has failed. The inverter continues to feed in. Corrective measures:
|
7105 | Parameter setting failed Parameters could not be set using the memory card. The inverter continues to feed in. Corrective measures:
|
7106 | Update file defective The update file is defective. The update failed. The inverter continues to feed in. |
7110 | No update file found No new update file was found on the SD memory card. The update failed. The inverter continues to feed in. |
7112 | Update file successfully copied |
7113 | The memory card is full or write-protected |
7201 7202 | Data storage not possible |
7303 | Host computer update failed The cause must be determined by the Service. Corrective measures:
|
7320 | The device was successfully updated The firmware update was completed successfully. |
7330 | Condition test failed The testing of the update conditions was not successful. The firmware update package is not suitable for this inverter. |
7331 | Update transport started Update file is being copied. |
7332 | Update transport successful Update file was copied successfully to the inverter's internal memory. |
7333 | Update transport failed Update file could not be copied to the inverter's internal memory. In the event of connection with the inverter via Wi-Fi network, a poor connection quality can be the cause. Corrective measures:
|
7341 | Update Bootloader The inverter is performing a bootloader update. |
7342 | Update Bootloader failed The bootloader update failed. Corrective measures:
|
7347 | Incompatible file The configuration file is not suitable for this inverter. Corrective measures:
|
7348 | Incorrect file format The configuration file is not of the required format or is damaged. Corrective measures:
|
7350 | Transfer of a configuration file has started The configuration file is being transferred. |
7351 | Update Wi-Fi The inverter is updating the Wi-Fi module. |
7352 | Update of Wi-Fi not successful The update of the Wi-Fi module failed. Corrective measures:
|
7353 | Update time zone database The inverter is updating the time zone database. |
7354 | Update of time zone database not successful The update of the time zone database failed. Corrective measures:
|
7355 | Update WebUI The inverter is updating the inverter user interface. |
7356 | Update of the WebUI not successful The update of the inverter user interface failed. Corrective measures:
|
7619 | Communication fault with meter unit > Check communication to meter The inverter is not receiving any data from the energy meter. Corrective measures:
|
7622 | No communication with the I/O module This event is displayed during a device-internal communication error with the SMA I/O Module. The inverter will disconnect from the utility grid for safety reasons. |
7702 | Device fault The cause must be determined by the Service. Corrective measures:
|
7801 | Fault overvoltage protector One or more surge arresters have tripped or one or more surge arresters are not inserted correctly. Corrective measures:
|
8003 | Active power limit Temperature The inverter has reduced its power output for more than 10 minutes due to excessive temperature. Corrective measures:
|
8101 8102 8103 8104 | Communication failure The cause must be determined by the Service. Corrective measures:
|
8208 | Self-test for arc fault detection: interference level too high An error has occurred during the self-test of the arc-fault circuit interrupter. The cause must be determined by the Service. Corrective measures:
|
8209 | Self-test for arc fault detection: interference level too low An error has occurred during the self-test of the arc-fault circuit interrupter. The cause must be determined by the Service. Corrective measures:
|
9002 | SMA Grid Guard code invalid The SMA Grid Guard code entered is incorrect. The operating parameters are still protected and cannot be changed. Corrective measures:
|
9003 | Grid parameters locked Changes to the grid parameters are now blocked. In order to be able to make changes to the grid parameters, from now on you must log in using the SMA Grid Guard code. |
9005 | Changing of grid parameters not possible > Ensure DC supply This error can have the following causes:
Corrective measures:
|
9007 | Abort self-test The self-test (Italy only) was terminated. Corrective measures:
|
9033 | Rapid Shutdown was triggered The inverter detected the triggering of a Rapid Shutdown. The AC side of the inverter was disconnected. |
9034 | Error in Rapid Shutdown System This message can have the following causes:
Corrective measures:
|
9035 | Rapid Shutdown successful The voltage at the DC inputs and at the AC output of the inverter was successfully discharged. |
9037 | Generator connection not carried out The PV array disconnect switches did not connect the PV generator. Corrective measures:
|
9038 | Redundant Rapid Shutdown discharge function not ensured The cause must be determined by the Service. Corrective measures:
|
10108 | Time adjusted / old time |
10109 | Time adjusted / new time |
10110 | Time synchronization failed: [xx] No time information could be called up from the set NTP server. Corrective measures:
|
10118 | Parameter upload complete The configuration file was loaded successfully. |
10248 | [Interface]: network busy The network is busy. Data exchange between the devices is not at an optimum and is greatly delayed. Corrective measures:
|
10249 | [Interface]: network overloaded The network is overloaded. There is no data exchange between the devices. Corrective measures:
|
10250 | [Interface]: package error rate [ok / high] The package error rate has changed. If the package error rate is high, the network is overloaded or the connection to the network switch or DHCP server (router) is impaired. Corrective measures if the package error rate is high:
|
10251 | [Interface]: communication status goes to [OK / Warning / Error / Not connected] The communication status to the network switch or DHCP server (router) has changed. An additional error message may be displayed. |
10252 | [Interface]: communication disrupted There is no valid signal on the network line. Corrective measures:
|
10253 | [Interface]: connection speed goes to [100 Mbit / 10 Mbit] The data transfer rate has changed. The cause for the status [10 Mbit] can be a defective plug, a defective cable or the pulling or plugging of the network connector. Corrective measures if the status is [10 Mbit]:
|
10254 | [Interface]: duplex mode goes to [Full / Half] The duplex mode (data transfer mode) has changed. The cause for the status [Half] can be a defective plug, a defective cable or the pulling or plugging of the network connector. Corrective measures if the status is [Half]:
|
10255 | [Interface]: Network load OK The network load has returned to a normal range after being busy. |
10282 | [User group]-Login via [protocol] locked After several incorrect login attempts, login has been blocked for a limited time. In this case, the User login will be blocked for 15 minutes, the Grid Guard login for 12 hours. Corrective measures:
|
10283 | Wi-Fi module faulty The Wi-Fi module integrated in the inverter is defective. Corrective measures:
|
10284 | No Wi-Fi connection possible The inverter does not currently have a Wi-Fi connection to the selected network. Corrective measures:
|
10285 | Wi-Fi connection established Connection to the selected Wi-Fi network has been established. |
10286 | Wi-Fi connection lost The inverter has lost Wi-Fi connection to the selected network. Corrective measures:
|
10339 | Webconnect enabled |
10340 | Webconnect disabled |
10431 | I-V curve measurement successfully carried out |
10502 | Active power limit AC frequency |
10513 | Grid management service Fast stop: Stop by system control is executed This event is generated by the monitoring relay of the monitoring unit when the grid and PV system protection device is triggered. The inverter disconnects from the utility grid. |
10901 | Start self-test |xx| |
10902 | Current disconnection limit for voltage increase protection |xxx| V |
10903 | Current disconnection limit for voltage monitoring lower maximum threshold |xxx| V |
10904 | Current disconnection limit for voltage monitoring upper minimum threshold |xxx| V |
10905 | Current disconnection limit for voltage monitoring middle minimum threshold |xxx| V |
10906 | Current disconnection limit for frequency monitoring switchable maximum threshold |xxx| Hz |
10907 | Current disconnection limit for frequency monitoring switchable minimum threshold |xxx| Hz |
10908 | Current disconnection limit for frequency monitoring lower maximum threshold |xxx| Hz |
10909 | Current disconnection limit for frequency monitoring upper minimum threshold |xxx| Hz |
10910 | Measured disconnection threshold for the running test point |xxx| |xx| |
10911 | Standard value for the running test point |xxx| |xx| |
10912 | Measured disconnection time for the running test point |xx| s |
27103 | Set parameter The parameter changes are being adopted. |
27104 | Parameters set successfully The parameter changes were successfully adopted. |
27107 | Update file OK The update file found is valid. |
27301 | Update communication The inverter is updating the communication component. |
27302 | Update main CPU The inverter is updating the inverter component. |
27312 | Update completed The inverter has successfully completed the update. |
29001 | Inst. code valid The entered Grid Guard code is valid. Protected parameters have now been unlocked and you can adjust the parameters. The parameters will be automatically locked again after 10 feed-in hours. |
29004 | Grid parameter unchanged Changing the grid parameters is not possible. |