Configuring the SMA I/O Module


Qualified person

If the SMA I/O Module is operated in the operating mode Active power limitation and feed-in operation has been interrupted by grid operator specification, you can set the option for the feed-in operation to remain interrupted until it is manually reactivated.

Procedure:

  1. Select the parameter group System and device control > Power control modules.
  2. Ensure that the parameter Operating mode is set to Active power limitation.
  3. Select the parameter group System and device control > Configuration of feed-in management.
  4. Set the parameter Grid disconnection for 0% feeding or 0W setpoint to Yes, with manual restart.
  5. Select the parameter Operating mode Active power and set the desired active power limitation.