Technical Data


DC input

Maximum PV array power

75000 Wp

Maximum input voltage

1000 V

Voltage range at 420 V AC/440 V AC

150 V to 1000 V

Rated input voltage

725 V

Minimum input voltage at 420 V AC/440 V AC

150 V

Initial input voltage at 420 V AC/440 V AC

188 V

Maximum input current per MPP input

20 A

Maximum input current per string

20 A

Maximum short-circuit current per MPP input

30 A

Number of independent MPP inputs

6

Strings per MPP input

2

AC Output

Rated power at 420 V/440 V, 50 Hz/60 Hz

50000 W

Maximum apparent AC power at 420 V/440 V

50000 VA

Nominal AC voltage

3 / grounding conductor; 420 V (50 Hz)

3 / PE; 440 V (60 Hz)

AC voltage range

350 V to 530 V

Nominal AC current at 420 V

69 A

Nominal AC current at 440 V

65.9 A

Maximum output current

72.5 A

Total harmonic distortion

3 %

Maximum output current under fault conditions

86 A

AC power frequency

50 Hz / 60 Hz

Operating range at AC grid frequency 50 Hz

44 Hz to 55 Hz

Operating range at AC grid frequency 60 Hz

54 Hz to 65 Hz

Power factor at rated power

1

Adjustable range of the power factor

0.0 overexcited to 0.0 underexcited

AC terminal

3 line conductors, 3 conductors

Surge category in accordance with IEC 62109-1

III

Multifunction relay

Maximum DC switching voltage

30 V

Maximum AC switching current

1.0 A

Maximum DC switching current

1.0 A

Minimum load

0.1 W

Minimum electrical endurance when the maximum switching voltage and maximum switching current are complied with*

100000 switching cycles

* Corresponds to 20 years at 12 switching operations per day

Efficiency

Efficiency in accordance with JIS C 8961

97.5 %

Maximum efficiency, ηmax

98.1 %

Protective devices

DC reverse polarity protection

Short-circuit diode

Input-side disconnection point

DC Load-Break Switch

DC overvoltage protection

Surge arrester type II (optional)

AC short-circuit current capability

Current control

Grid monitoring

OV, UV, OF, UF

Maximum cut-off current of the circuit breaker

100 A

Ground fault monitoring

Insulation monitoring: Riso > 34 kΩ

All-pole sensitive residual-current monitoring unit

Available

Islanding detection

Active and passive

General Data

Width x height x depth, without feet or DC load-break switch

569 mm x 733 mm x 621 mm

Weight

84 kg

Length x width x height of the packaging

800 mm x 600 mm x 886 mm

Transport weight

100 kg

Climatic category in accordance with IEC 60721-3-4

4K4H

Operating temperature range

-25°C to +60°C

Maximum relative humidity, (condensing)

100 %

Maximum operating altitude above mean sea level (MSL)

3000 m

Typical noise emission

64 dB(A)

Power loss in night mode

5 W

Topology

Transformerless

Cooling method

SMA OptiCool

Number of fans

3

Degree of protection for electronics in accordance with IEC 60529

IP65

Protection class in accordance with IEC 62109-1

I

WLAN standard

WLAN 802.11 b/g/n

WLAn radio spectrum

2.4 GHz

Maximum transmission power

100 mW

Wi-Fi range in free-field conditions

100 m

Quantity maximum detectable Wi-Fi networks

32

Climatic conditions

Installation in accordance with IEC 60721-3-4, Class 4K4H

Extended temperature range

-25 °C to +60 °C

Extended humidity range

0 % to 100 %

Threshold for relative humidity, non-condensing

100 %

Extended air pressure range

 79.5 kPa to 106 kPa

Transport in accordance with IEC 60721-3-4, Class 2K3

Temperature range

-40°C to +70°C

Equipment

DC terminal

SUNCLIX DC connector

AC terminal

Screw terminals

Multifunction relay

As standard

Surge protection devices for AC and/or DC

Optional

Torques

Screws for the DC-Connection Unit and AC-Connection Unit enclosure lids

6 Nm

Screws for AC terminals with conductor cross-section of 35 mm² to 95 mm²

20 Nm

Screws for AC terminals with conductor cross-section of 120 mm²

30 Nm

Screws for attaching the feet or profile rails

16 Nm

Screws for the cover on the top of the inverter

6 Nm

Counter nut of M63 cable gland

14 Nm

Swivel nut for M63 cable gland

33 Nm

Swivel nut for M32 cable gland

5 Nm

SUNCLIX swivel nut

2 Nm

Data Storage Capacity

Daily energy yields

63 days

Daily yields

30 years

Event messages for users

1024 events

Event messages for installers

1024 events