Utility Grid


Only utility grid permitted as external energy source

The only permitted external energy source in the battery-backup grid is the utility grid. Even when using the Sunny Island, the battery-backup system does not support the operation with a generator (e.g. diesel generator).

Residual-current monitoring unit:

If an external residual-current device is required, install a residual-current device which trips at a residual current of 100 mA or higher (for details on selecting a residual-current device, see the Technical Information "Criteria for Selecting a Residual-Current Device" at www.SMA-Solar.com).

Special conditions for use of the battery-backup grid with Sunny Island in Belgium

The utility grid connected to the automatic transfer switching device must generally be a TN or TT system. In Belgium, the utility grid can be designed to function as an IT system that is, however, grounded to the neutral point of the source.

This results in a hybrid form of an IT and TT system. Compared with a TT system, this hybrid form is not equipped with a neutral conductor. With this installation, the following restriction applies when using the battery-backup system:

  1. If the utility grid functions as an IT system that is grounded to the neutral point of the source, the connected battery-backup system must be single-phase.

Characteristics of the battery-backup grid

Characteristic

Single-phase battery-backup grid with Sunny Island

Three-phase battery-backup grid with Sunny Island

Three-phase battery-backup grid with Sunny Tripower Smart Energy

Single-phase battery-backup grid with Sunny Boy Smart Energy

Three-phase battery-backup grid with Sunny Boy Smart Energy

Utility grid

TN or TT
System

TN or TT
System

TN or TT
System

TN or TT
System

TN system

Single-phase or three-phase

Three-phase

3-phase

Single-phase

Three-phase

Behavior of the battery inverters in the event of grid failure

1 Sunny Island supplies the battery-backup grid.

Three Sunny Island inverters switched in parallel on the DC side supply each line conductor with the corresponding phase.

Sunny Tripower Smart Energy supplies the battery-backup grid.

Sunny Boy Smart Energy supplies the battery-backup grid.

Sunny Boy Smart Energy supplies the battery-backup grid.

Recognition of grid failure

Grid failure is only recognized on the line conductor which is connected to the battery inverter (e.g. L1).

Grid failure is recognized on all line conductors.

Grid failure is recognized on all line conductors.

Grid failure is recognized on the connecting phase.

Grid failure is recognized on the connecting phase.

Supply of the loads in the event of grid failure

All connected single-phase loads are supplied (e.g. the loads connected to L1).

All loads are supplied.

The loads connected to the battery-backup grid are supplied.

All connected loads are supplied.

All connected single-phase loads are supplied.

Grid feed-in by the PV inverters in the event of grid failure

Only single-phase PV inverters can feed energy into the grid.

Single-phase and three-phase PV inverters can feed energy into the grid.

Only the three-phase Sunny Tripower Smart Energy can provide a grid in the event of a grid failure and feed in.

Only the single-phase Sunny Boy Smart Energy can provide a grid and further single-phase PV or hybrid inverters can feed in additionally.

Only the single-phase Sunny Boy Smart Energy can provide a grid and further single-phase PV or hybrid inverters can feed in additionally.

Phase coupling in the battery-backup grid

Phase coupling is possible in a three-phase grid.

Phase coupling is not possible.

Phase coupling is not necessary.

Phase coupling is not possible.

Phase coupling is possible.

Rotating magnetic field in the battery-backup grid

No: even with phase coupling, the battery-backup grid remains single-phase.

Yes: three Sunny Island inverters form a three-phase battery backup grid with rotating magnetic field.

Yes: one Sunny Tripower Smart Energy provides a three-phase battery-backup grid with rotating magnetic field.

No: even with phase coupling, the battery-backup grid remains single-phase.

No: even with phase coupling, the battery-backup grid remains single-phase.

Phase coupling

If three-phase loads are connected to a single-phase utility grid with phase coupling, SMA Solar Technology AG cannot rule out damage to the three-phase loads. With phase coupling, single-phase loads only must be connected to the battery-backup grid.

Designing the neutral conductor cross-section for the current of the single-phase inverter

To prevent overload of the neutral conductor, the cross-section of the neutral conductor must be designed to match the current of the single-phase inverter.

Battery-backup grid with or without all-pole disconnection

Type of grid disconnection

All-pole disconnection

Non-all-pole disconnection

Operating principle

In the event of grid failure, a tie switch disconnects all line conductors and the neutral conductor from the utility grid.

In the event of grid failure, a tie switch disconnects all line conductors from the utility grid. The neutral conductor of the battery-backup grid remains permanently connected to the utility grid.

Criterion for use

If the technical connection requirements of the grid operator or the locally applicable standards and directives call for all-pole disconnection, you must install the battery-backup system with all-pole disconnection.

If the technical connection requirements of the grid operator or the locally applicable standards and directives prohibit disconnection of the neutral conductor, you must install the battery-backup system without all-pole disconnection.