Requirements on the SPS OUT AC cable for connection to the inverter
The cable length and quality affect the quality of the signal. Observe the following cable requirements:
Conductor type: copper wire
Permissible temperature: at least 90°C (194°F)
The conductors must be solid or stranded wire.
Conductor cross-section: 1.5 mm² to 2.5 mm² (16 AWG to 14 AWG)
Insulation stripping length: 6 mm
Nominal voltage: at least 600 V
Maximum length of conductors: 30 m (98 ft)
The conductors with regards to their ampacity, rated temperatures, operating conditions and power loss must be made in accordance with the local standards and the National Electrical Code® ANSI/NFPA 70. If the manufacturer (SMA Solar Technology AG) requires a higher conductor cross-section than the standard, the range of the manufacturer must be observed.