SPS IN signal cable requirements


The cable length and quality affect the quality of the signal. Observe the following cable requirements:

  • Conductor type: copper wire

  • Permissible temperature: at least 90°C (194°F)

  • The conductors must be solid or stranded wire.

  • Conductor cross-section: 0.8 mm² to 1.5 mm² (18 AWG to 16 AWG)

  • Insulation stripping length: 6 mm

  • Nominal voltage: at least 600 V

  • Maximum length of conductors: 30 m (98 ft)

  • The conductors with regards to their ampacity, rated temperatures, operating conditions and power loss must be made in accordance with the local standards and the National Electrical Code® ANSI/NFPA 70. If the manufacturer (SMA Solar Technology AG) requires a higher conductor cross-section than the standard, the range of the manufacturer must be observed.