General Data
Width x height x depth | 435 mm x 470 mm x 176 mm |
Weight | 17 kg |
Length x width x height of the packaging | 495 mm x 595 mm x 250 mm |
Transport weight | 21.8 kg |
Climatic category in accordance with IEC 60721-3-4 | 4K4H |
Environmental category | outdoors |
Pollution degree outside the enclosure | 3 |
Pollution degree inside the enclosure | 2 |
Operating temperature range | -25°C to +60°C |
Max. permissible value for relative humidity (condensing) | 100 % |
Maximum operating altitude above mean sea level (MSL) | 3000 m |
Typical noise emission | 30 dB(A) |
Power loss in night mode | 5 W |
Maximum data volume per inverter with Speedwire/Webconnect | 550 MB/month |
Additional data volume when using the Sunny Portal live interface | 660 kB/hour |
Power control / Demand response (DRED) | Communication via Modbus interface |
Export limiting in accordance with AS/NZS 4777.2 | EMETER-20, HM-20 |
Demand response mode in accordance with AS/NZS 4777.2 | DRM0 |
Topology | Transformerless (Non-isolated) |
Cooling method | Convection |
Degree of protection for electronics in accordance with IEC 60529 | IP65 |
Protection class in accordance with IEC 62109-1 | I |
Radio technology | WLAN 802.11 b/g/n |
Radio spectrum | 2.4 GHz |
Maximum transmission power | 100 mW |
Quantity maximum detectable Wi-Fi networks | 32 |
Grid configurations1) | IT, Delta-IT, TN-C, TN-S, TN-C-S, TT (when VN_PE < 20 V) |
1) IT, Delta-IT: When using in these systems, the grounding conductor monitoring must be deactivated and an additional grounding connected to the inverter.