Sunny Boy 3000TL / 3600TL
DC Input
SB 3000TL-21 |
SB 3600TL-21 | |
---|---|---|
Maximum DC power at cos φ = 1 |
3,200 W |
3,880 W |
Maximum input voltage |
750 V |
750 V |
MPP voltage range |
175 V to 500 V |
175 V to 500 V |
Rated input voltage |
400 V |
400 V |
Minimum input voltage |
125 V |
125 V |
Initial input voltage |
150 V |
150 V |
Maximum input current, input A |
15 A |
15 A |
Maximum input current, input B |
15 A |
15 A |
Maximum short-circuit current per input* |
20 A |
20 A |
Maximum reverse current from the inverter in the system for max. 1 ms |
0 A |
0 A |
Number of independent MPP inputs |
2 |
2 |
Strings per MPP input |
2 |
2 |
Overvoltage category in accordance with IEC 60664-1 |
II |
II |
* In accordance with IEC 62109-2: ISC PV
AC Output
SB 3000TL-21 |
SB 3600TL-21 | |
---|---|---|
Rated power at 230 V, 50 Hz |
3,000 W |
3,680 W |
Maximum apparent AC power |
3,000 VA |
3,680 VA |
Rated grid voltage |
230 V |
230 V |
Nominal AC voltage |
220 V / 230 V / 240 V |
220 V / 230 V / 240 V |
AC voltage range* |
180 V to 280 V |
180 V to 280 V |
Nominal AC current at 220 V |
13.6 A |
16.0 A |
Nominal AC current at 230 V |
13.0 A |
16.0 A |
Nominal AC current at 240 V |
12.5 A |
15.3 A |
Maximum output current |
16 A |
16 A |
Total harmonic distortion of the output current with total harmonic distortion of the AC voltage < 2%, and AC power > 50% of the rated power |
≤4% |
≤4% |
Inrush current |
< 20% of the nominal AC current for a maximum of 10 ms |
< 20% of the nominal AC current for a maximum of 10 ms |
Maximum output current under fault conditions |
34 A |
34 A |
Rated power frequency |
50 Hz |
50 Hz |
AC power frequency* |
50 Hz / 60 Hz |
50 Hz / 60 Hz |
Operating range at AC power frequency 50 Hz |
45 Hz to 55 Hz |
45 Hz to 55 Hz |
Operating range at AC power frequency 60 Hz |
55 Hz to 65 Hz |
55 Hz to 65 Hz |
Power factor at rated power |
1 |
1 |
Displacement power factor cos φ, adjustable |
0.8 underexcited to 1 to 0.8 overexcited |
0.8 underexcited to 1 to 0.8 overexcited |
Feed-in phases |
1 |
1 |
Connection phases |
1 |
1 |
Overvoltage category in accordance with IEC 60664-1 |
III |
III |
* depending on the configured country data set
Efficiency
SB 3000TL-21 |
SB 3600TL-21 | |
---|---|---|
Maximum efficiency, ηmax |
97.0% |
97.0% |
European weighted efficiency, ηEU |
96.0% |
96.4% |