Commissioning Procedure


Qualified person

Before you can commission the inverter, you must check various settings and make changes if necessary. This section describes the procedure and gives an overview of the steps, which must always be performed in the prescribed sequence.

Procedure

See

Connect to the communication interface.

Installation manual of the communication interface

Check the country data set configuration of the inverter.

Supplementary sheet with the default settings, type label or display

If the country data set is not set correctly for your country or your purpose, adjust to the required country data set and the corresponding display language within the first ten feed-in hours via the rotary switches in the inverter.

Configuring the Country Data Set

If the inverter is to communicate with several BLUETOOTH devices, or if BLUETOOTH is not to be used as a type of communication, set the NetID.

Setting the NetID

Commission the inverter and start a self-test, if required.

Commissioning the Inverter and Self-Test in Accordance with CEI 0-21 for PV Systems ≤6 kW