Protective Devices


DC reverse polarity protection

Short-circuit diode

Input-side disconnection point

Electronic Solar Switch, SUNCLIX DC connector

DC overvoltage protection

Thermally monitored varistors

AC short-circuit current capability

Current control

Grid monitoring

SMA Grid Guard 3

Maximum permissible fuse protection for SB 3000TL-21

25 A

Maximum permissible fuse protection for SB 3600TL-21

32 A

Maximum permissible fuse protection for SB 4000TL-21

32 A

Maximum permissible fuse protection for SB 5000TL-21

32 A

Ground-fault monitoring for SB 3000TL-21

Insulation monitoring: Riso > 625 kΩ

Ground-fault monitoring for SB 3600TL-21

Insulation monitoring: Riso > 550 kΩ

Ground-fault monitoring for SB 4000TL-21

Insulation monitoring: Riso > 500 kΩ

Ground-fault monitoring for SB 5000TL-21

Insulation monitoring: Riso > 400 kΩ

All-pole sensitive residual-current monitoring unit

Available