General Data
Width x height x depth, without Electronic Solar Switch |
490 mm x 490 mm x 185 mm |
Width x height x depth, with Electronic Solar Switch |
490 mm x 519 mm x 185 mm |
Weight |
26 kg |
Length x width x height of the packaging |
597 mm x 617 mm x 266 mm |
Transport weight |
30 kg |
Climatic category in accordance with IEC 60721-3-4 |
4K4H |
Environmental category |
Outdoors |
Pollution degree outside the enclosure |
3 |
Pollution degree inside the enclosure |
2 |
Operating temperature range |
-25°C to +60°C |
Maximum permissible value for relative humidity, non-condensing |
100% |
Maximum operating altitude above mean sea level (MSL) |
2,000 m |
Typical noise emission |
25 dB(A) |
Power loss in night mode |
<1 W |
Maximum data volume per inverter with Speedwire/Webconnect |
550 MB/month |
Additional data volume when using the Sunny Portal live interface |
660 kB/hour |
Topology |
Transformerless |
Cooling method |
Convection |
Degree of protection for electronics in accordance with IEC 60529 |
IP65 |
Protection class in accordance with IEC 61140 |
I |
Grid configurations* |
IT, Delta-IT, TN-C, TN-S, TN-C-S, split phase, TT (if VN_PE < 20 V) |
Approvals and national standards, as per 10/2014** |
AS4777:2005, CE, CEI 0-21, C10/11:2012, DIN EN 62109-1, EN 50438:2013, G59/3, G83/2, IEC 61727, IEC 62109-1, IEC 62109-2, IEC 62116, NRS 97-2-1, PPC, PPDS, RD 661/2007, RD 1699:2011, SI4777, TOR D4, VDE 0124-100, VDE0126-1-1:2006, VDE0126-1-1 / UTE C15-712-1, VDE-AR-N 4105, VFR 2014 |
* IT, Delta-IT: When using in these systems, the grounding conductor monitoring must be deactivated and an additional grounding connected to the inverter.
** EN 50438: does not apply to all national appendices of EN 50438
IEC 62109-2: This standard requires that either the multifunction relay in the inverter is used as fault indicator or that the inverter is connected to Sunny Portal and that the fault alert is activated in Sunny Portal.
NRS 97-2-1: This standard requires a separate label attached to the AC distribution board which indicates the AC-side disconnection of the inverter in case of a grid failure (for further details, see NRS 97-2-1, Sect. 4.2.7.1 and 4.2.7.2)
RD 661/2007, RD 1699:2011:Contact the Service for restrictions in specific regions( > Contact).