Connecting the cables to BU-STPH-4P63B


Requirement:

  • The lid of the enclosure on the automatic transfer switching device has been opened or removed.
  • The installation cover of the automatic transfer switching device has been removed.

    Procedure:

    1. Disconnect the inverter from all voltage sources (see inverter manual).
    2. Switch off the battery (see battery manual).
    3. Switch off the AC fuse in the meter cabinet.
    4. 16911960460
    5. Connect conductor PE for connection to the utility grid to the PE terminal on the automatic transfer switching device. To do this, unlock the terminal with a suitable tool (blade width 5.5 mm).
    6. 16911961612
    7. Connect conductor N for connection to the utility grid to the N terminal on the automatic transfer switching device. To do this, unlock the terminal with a suitable tool (blade width 5.5 mm).
    8. 16911961740
    9. Connect conductors L1, L2 and L3 for the connections to the utility grid to the GRID L1, GRID L2 and GRID L3 terminals on the automatic transfer switching device. To do this, unlock the terminals with a suitable tool (blade width 5.5 mm).
    10. 16911961356
    11. Connect conductor PE for the connection of the backup loads to the PE terminal on the automatic transfer switching device. To do this, unlock the terminal with a suitable tool (blade width 5.5 mm).
    12. 16911961484
    13. Connect conductor N for the connection of the backup loads to the N terminal on the automatic transfer switching device. To do this, unlock the terminal with a suitable tool (blade width 5.5 mm).
    14. 16911962124
    15. Connect conductors L1, L2 and L3 for the backup loads to the Backup L1, Backup L2 and Backup L3 terminals on the automatic transfer switching device. To do this, unlock the terminals with a suitable tool (blade width 5.5 mm).
    16. 16911962508
    17. Connect the SPS OUT AC cable to the L and N terminals on the automatic transfer switching device as labeled. To do this, unlock the terminal with a suitable tool (blade width 3.5 mm).
    18. 16911962636

    19. Connect the SPS IN AC cable to the 1 and 2 terminals on the automatic transfer switching device as labeled. To do this, unlock the terminal with a suitable tool (blade width 3.5 mm).
    20. Ensure that all conductors are securely in place.