Requirements on the SPS OUT AC cable for connection to the inverter


  • Conductor type: copper wire

  • The conductors must be solid or stranded wire.

  • Conductor cross-section when using solid or stranded wire without bootlace ferrules: 1.5 mm² to 2.5 mm²

  • Conductor cross-section when using bootlace ferrules: 1.5 mm² to 2.5 mm²

  • Outer diameter: max. 9 mm

  • Insulation stripping length: 8 mm to 10 mm

  • Maximum length of conductors: 30 m

  • Do not lay the SPS input and SPS output lines together in one cable