Requirements on the SPS OUT AC cable for connection to the inverter
Conductor type: copper wire
The conductors must be solid or stranded wire.
Conductor cross-section when using solid or stranded wire without bootlace ferrules: 1.5 mm² to 2.5 mm²
Conductor cross-section when using bootlace ferrules: 1.5 mm² to 2.5 mm²
Outer diameter: max. 9 mm
Insulation stripping length: 8 mm to 10 mm
Maximum length of conductors: 30 m
Do not lay the SPS input and SPS output lines together in one cable