Connecting the connections to the automatic transfer switching device


Qualified person

Requirements:

  • The lid of the enclosure of the automatic transfer switching device has been opened or removed.

  • The installation cover of the automatic transfer switching device has been removed.

Procedure:

  1. Disconnect the inverter from voltage sources (see inverter manual).
  2. Switch off the battery (see battery manual).
  3. Switch off the AC fuse in the meter cabinet.
  4. 15048369804
  5. Connect the grounding cable to the connection on the automatic transfer switching device. To do this, unlock the terminal with a suitable tool (blade width 5.5 mm).
  6. 15030056332
  7. Connect conductor N for connection to the utility grid to the GRID N connection on the automatic transfer switching device. To do this, unlock the terminal with a suitable tool (blade width 5.5 mm).
  8. 15030054284
  9. Connect conductor L1 for connection to the utility grid to the GRID L1 connection on the automatic transfer switching device. To do this, unlock the terminal with a suitable tool (blade width 5.5 mm).
  10. 15030052236
  11. Connect conductor L1 for the backup loads to the LOAD L1 connection on the automatic transfer switching device. To do this, unlock the terminal with a suitable tool (blade width 5.5 mm).
  12. 15254991884
  13. Connect conductor N for the backup loads to the LOAD N connection on the automatic transfer switching device. To do this, unlock the terminal with a suitable tool (blade width 5.5 mm).
  14. 15298320268
  15. Connect conductor N to the INV N connection on the fuse block in the automatic transfer switching device.
  16. 15298320652
  17. Connect conductor L1 to the INV L1 connection on the fuse block in the automatic transfer switching device.
  18. Connect conductors L1, N and PE to the inverter (see inverter manual).
  19. 15030007308
  20. Connect the SPS OUT AC cable to the L and N connections on the automatic transfer switching device as labeled. To do this, unlock the terminal with a suitable tool (blade width 3.5 mm).
  21. 15030004876
  22. Connect the SPS IN AC cable to the 1 and 2 connections on the automatic transfer switching device as labeled. To do this, unlock the terminal with a suitable tool (blade width 3.5 mm).
  23. Tug lightly to ensure that all conductors are secured in the terminals.