Optional: Connecting residual-current device


Qualified person

In some countries, a residual-current device must be installed on the supply side of the inverter. You have the option of installing a residual-current device in the enclosure of the automatic transfer switching device. Space is provided for this on the DIN rails. The residual-current device must be coupled to ensure common tripping.

Additionally required material:

  • 2 suitable cables

Requirements:

  • There is sufficient space for the fuse block in the enclosure of the automatic transfer switching device.

Procedure:

  1. Disconnect the inverter from voltage sources (see inverter manual).
  2. Switch off the battery (see manual from the battery manufacturer).
  3. Disconnect the automatic transfer switching device from voltage sources.
  4. 15298373132
  5. Connect the residual-current device.
  6. Pull the cables as a test to ensure that all conductors are secured in the terminals.