Optional: Connecting additional Energy Meter CT and additional miniature circuit breakers
Qualified person
You have the option of expanding the automatic transfer switching device with an Energy Meter CT and additional miniature circuit-breakers. Space is provided for this on the DIN rails.
Requirements:
There is sufficient space in the enclosure of the automatic transfer switching device.
Procedure:
- Disconnect the inverter from voltage sources (see inverter manual).
- Switch off the battery (see manual from the battery manufacturer).
- Disconnect the automatic transfer switching device from voltage sources.
- Connect Energy Meter CT or additional miniature circuit breakers.
- Pull the cables as a test to ensure that all conductors are secured in the terminals.