Activating String-Failure Detection
Qualified person

Identical alignment of the PV modules with activated string-failure detection
If you would like to activate the string-failure detection, the PV modules of input A and input B must be aligned identically and the input voltage must be at least 188 V. Thus, reversed polarity of the DC connection or a defective string will be recognized by the inverter.
- Ensure that all PV modules are aligned identically.
- Ensure that the input voltage is at least 188 V.
If identically aligned PV modules are connected to input A and input B of the inverter, you can activate the self-learning string-failure detection and/or the substring-failure detection.
The basic procedure for changing operating parameters is explained in another section ( > Changing Operating Parameters).
Procedure:
-
To activate string-failure detection, select the parameter Operating mode of string failure detection or Op.PvProMod and set to Detect string failures or StrgFltDet.
-
To activate string-failure detection and substring-failure detection, select the parameter Operating mode of string failure detection or Op.PvProMod and set to Detect partial string failures or PaStrgFltDet.