Connecting RS485 devices to X2


Requirements:

  • The same baud rate (1200 baud, 9600 baud or 19200 baud) must be set in all RS485 devices.

Procedure:

  1. Dismantle 40 mm of the product end of the RS485 cable.
  2. Strip the shielding to the same length as the cable sheath.
  3. Shorten unused insulated conductors flush with the cable sheath.
  4. Strip off the conductor insulation by 6 mm.
  5. 16104341900
  6. Release the conductor entries on the supplied six-pole plug.
  7. 16104382348
  8. Connect the RS485 data cable conductors to the supplied six-pole plug. To do so, plug the conductors into the conductor entries and close the conductor entries. Observe the connector assignment.
  9. 16104342668
  10. If the product is at the end of the RS485 bus, install a jumper wire as a line terminator between pin 5 and pin 6 on the six-pole plug.
  11. 16104343052
  12. Plug the six-pole plug into the port X2 on the product.