Connecting signal source to X3
Additionally required material:
Digital signal source with up to 4 potential-free contacts
1 connection cable
Requirements:
The signal source must be technically suitable for connection to the digital inputs.
The connected digital signal source has a safe separation to the grid potential. When connecting the digital signal source the potential-free contact or an external potential-free contact is used.
The connection cable must be prepared for connection to the multipole terminal block.
Procedure:
- Connect the connection cable to the digital signal source (see the manual from manufacturer).
- Connect the connection cable to the supplied six-pole plug. For this, unlock the required terminal positions using a suitable tool and plug the conductors into these terminal positions.
- Connect the six-pole plug to terminal X3. Observe the pin assignment.
- Note the terminal assignment.