Configuring active and reactive power setpoints
NOTICE
Responsibility of the system operator for grid management service specifications
The system operator is responsible for the correctness of the configurations and information on grid management services and system power. Incorrect settings and specifications can result in device and system damages.
- Set the grid management service specifications required by the grid operator and laid down in the standards correctly. Contact the grid operator if necessary.
- Enter correct values for system power. Adjust the values for system power during system expansions.
- Ensure that all required default values are applied or sent cyclically.

Supported inverters for the limitation of the active power feed-in to 0%
The limitation of the active power feed-in to 0% are only supported by inverters that support the fallback function. In the event of a communication failure between the product and the inverter, the inverter is reduced to an output power of 0% during fallback). For more information see the inverter manual at www.SMA-Solar.com.
Requirements:
The configuration for the active power limitation must be agreed upon with the responsible grid operator.
There must be an appropriate energy meter installed at the grid-connection point within the system.
The user interface must be open and you must be logged in as Installer.
Procedure:
- Select the system in the focus navigation.
- Select the menu item Grid management service in the menu Configuration.
- Select the button Configuration & activation in the Active and reactive power row.
- The installation assistant will open.
- Make the settings for Grid settings, Active power and Reactive power according to the specifications required by the grid operator and laid down in the standards and confirm each with [Next].
- Click on [Save].