AC cable requirements
Aluminum or copper cables must be used.
The conductors must be solid, stranded or fine-stranded. When using fine-stranded wires, bootlace ferrules must be used.
The maximum permitted temperature of the terminal block for AC connection of 90°C (194°F) must be observed.
Conductor cross-section: 16 mm² to 95 mm² (3/0 AWG to 6 AWG)
External diameter: 35 mm to 48 mm (1.4 in to 1.9 in)
Insulation stripping length: 30 mm (1.18 in)
Sheath stripping length: ≤ 375 mm (14.76 in)
The cable and conductor cross-sections must always be dimensioned according to the local and national directives and within the range specified by the manufacturer (SMA Solar Technology AG)." If the manufacturer (SMA Solar Technology AG) requires a higher conductor cross-section than the standard, the range of the manufacturer must be observed. Examples of factors influencing cable dimensioning are: nominal AC current, type of cable, routing method, cable bundling, ambient temperature and maximum desired line losses (for calculation of line losses, see the design software "Sunny Design" from software version 2.0 at www.SMA-Solar.com).