Configuring the Country Data Set
Qualified person
By default, the inverter is set to a universally valid country data set. You will need to configure the country data set associated with the installation site and intended use before the product can begin operations. As long as no country data set is set, operation of the product will remain stopped. This state is signaled by the green and red LEDs flashing simultaneously. Once configuration of the product is completed, the product will start operating automatically.
The following tables provide an overview of the configurable country data sets based on the standards applicable in the location in question:
Standard | Configurable country data set |
---|---|
UL 1741 SA | [US] UL1741/2010/277 |
IEEE1547-2018/UL1741SB | [US] IEEE 1547:2018, Cat.B-II (from firmware version ≥ 4.1.1.R) [US] IEEE 1547:2018, Cat.B-III (from firmware version ≥ 4.1.1.R) [US] HECO SRD2.0 IEEE1547:2018 Cat.B-III (from firmware version ≥ 4.1.1.R) |
The basic procedure for changing operating parameters is explained in another section ( > Changing Operating Parameters).
Procedure:
In the parameter group Grid monitoring > Grid monitoring select the parameter Set country standard and set the required country data set.