Adjustable parameters for voltage and frequency monitoring


Qualified person

You can set the following parameters for voltage and frequency monitoring via the user interface of the inverter.

Name

Value/range

Default value

Voltage monitoring, peak voltage threshold

1.5 p.u. to 3 p.u.

1.78 p.u.

Voltage monitoring, peak voltage threshold tripping time

0.1 ms to 5 ms

0.312 ms

Voltage monitoring, upper maximum threshold

1 p.u. to 2 p.u.

1.2 p.u.

Voltage monitoring, lower min. threshold trip. time

0 ms to 1000000 ms

160 ms

Voltage monitoring, median maximum threshold

1 p.u. to 2 p.u.

1.1 p.u.

Voltage monitoring, median max. threshold trip.time

0 ms to 1000000 ms

2000 ms1)

13000 ms2)

Voltage monitoring, lower maximum threshold

1 p.u. to 2 p.u.

1.1 p.u.

Voltage monitoring, lower max. threshold trip. time

0 ms to 1000000 ms

1000000 ms

Voltage monitoring, upper minimum threshold

0 p.u. to 1 p.u.

0.70 p.u.1)

0.88 p.u.2)

Voltage monitoring, lower min. threshold trip. time

0 ms to 1000000 ms

1000000 ms

Voltage monitoring, median minimum threshold

0 p.u. to 1 p.u.

0.70 p.u.1)

0.88 p.u.2)

Voltage monitoring, median min. threshold trip.time

0 ms to 1000000 ms

10000 ms1)

21000 ms2)

Voltage monitoring, lower minimum threshold

0 p.u. to 1 p.u.

0.45 p.u.1)

0.5 p.u.2)

Voltage monitoring, lower min. threshold trip. time

0 ms to 1000000 ms

160 ms1)

2000 ms2)

Frequency monitoring upper maximum threshold

50 Hz to 66 Hz

62 Hz

Frequency monitoring upper max. threshold trip. time

0 ms to 1000000 ms

160 ms

Frequency monitoring, lower maximum threshold

50 Hz to 66 Hz

61.2 Hz

Frequency monitoring, lower max. threshold trip. time

0 ms to 1000000 ms

300000 ms

Frequency monitoring upper minimum threshold

44 Hz to 60 Hz

58.5 Hz

Frequency monitoring, upper min. threshold trip. time

0 ms to 1000000 ms

300000 ms

Frequency monitoring, lower minimum threshold

44 Hz to 60 Hz

56.5 Hz

Frequency monitoring, lower min. threshold trip. time

0 ms to 1000000 ms

160 ms

Volt. increase prot.

1 to 2

2 p.u.

Voltage increase protection trigger time

40 ms to 10000 ms

10000 ms

Min. voltage for reconnection

0 p.u. to 1 p.u.

0.917 p.u.

Max. voltage for reconnection

2 p.u. to 2 p.u.

1.05 p.u.

Minimum switching frequency

44 Hz to 60 Hz

59.5 Hz

Maximum switching frequency

50 Hz to 66 Hz

60.1 Hz

1) Default value in the country data set IEEE 1547:2018, Cat.B-II