AC cable requirements
Aluminum or copper cables must be used.
The conductors must be solid, stranded or fine-stranded. When using fine-stranded wire, bootlace ferrules must be used.
The maximum permitted temperature for the terminal block of the AC connection of 90°C must be observed.
Conductor cross-section: 16 mm² to 95 mm² (3/0 AWG to 6 AWG)
External diameter: 35 mm to 48 mm (1.4 in to 1.9 in)
Insulation stripping length: 30 mm (1.18 in)
Sheath stripping length: ≤ 375 mm (14.76 in)