Resetting the Operation Inhibition after Detection of an Arc Fault


Qualified person

If the red LED is glowing and the event number 4301 is shown on the display and/or in the event list on the user interface of the inverter, the inverter has detected an electric arc and interrupts feed-in operation.

There are two options for resetting the operation inhibition:

  • Reset the operation inhibition by tapping twice on the enclosure lid of the Connection Unit.

  • Reset the operation inhibition by parameter setting.

Reset the operation inhibition by tapping twice on the enclosure lid of the Connection Unit

  1. DANGER

    Danger to life due to electric shock

    1. Disconnect the inverter from any voltage sources (see the inverter installation manual).
  2. Ensure that the PV modules, the connected DC cables and the terminal block for the DC connection are not defective.
  3. Repair or replace defective PV modules, DC cables or terminal block for the DC connection.

  4. Recommission the inverter (see inverter installation manual).
  5. If the event with the event number 4301 appears in the display, immediately tap on the enclosure lid twice in quick succession. Here, the operation inhibition can only be reset if the event is showing in the display when you begin tapping.
  • This effects resetting of the operation inhibition and the inverter will start feeding in again. At the same time, the blue LED can flash rapidly, indicating that there is an active WPS function. The WPS function deactivates automatically after a short period.

Reset the operation inhibition by parameter setting

  1. DANGER

    Danger to life due to electric shock

    1. Disconnect the inverter from any voltage sources (see the inverter installation manual).
  2. Ensure that the PV modules, the connected DC cables and the terminal block for the DC connection are not defective.
  3. Repair or replace defective PV modules, DC cables or terminal block for the DC connection.

  4. Recommission the inverter (see inverter installation manual).
  5. Activate the user interface Establishing a connection to the user interface).
  6. Log into the user interface as an Installer Logging In and Out of the User Interface).
  7. Reset the operation inhibition by setting one of the following parameters:
    • Select the parameter Reset operating data and set to Reset operation inhibition.

      or

    • Select the parameter AFCI switched on and set to No and then back to Yes.

  • This effects resetting of the operation inhibition and the inverter will start feeding in again.