Switching Digital Outputs Based on Thresholds
The digital outputs of connected I/O systems can be switched depending on measured values or states. In this way, heat pumps or relays, for example, can be controlled by specifying a defined output. A tolerance (hysteresis) dependent on the selected operator prevents the digital outputs from switching even with slight power fluctuations.
Operator | Tolerance |
---|---|
Greater than or equal to (>=) | 1 % |
Less than or equal to (<=) | 1 % |
Equal to | 5 % |
Requirements:
-
All devices in the local network must be in operation and connected to the product via an Internet router.
-
All devices must support the Speedwire encryption.
Procedure:
- Log into the user interface of the Data Manager.
- Select the menu item Grid management services in the menu Configuration.
- Select the button To the configuration in the Assigning analog outputs row.
- To configure the digital outputs of a connected device, select the button .
- Fill out the entry fields and select [Save].