Usable power with Battery-Box HVM+


HVM+ 8.3

HVM+ 11.0

HVM+ 13.8

Voltage range of battery

120 V to 172 V

160 V to 230 V

200 V to 288 V

Maximum current

50 A

Maximum battery power

8.6 kW

11.5 kW

14.4 kW

Maximum charge / discharge capacity STPH5-60

8.6 kW / 5 kW

10 kW / 5 kW

10 kW / 5 kW

Maximum charge / discharge capacity STPH6-60

8.6 kW / 6 kW

10 kW / 6 kW

10 kW / 6 kW

Maximum charge / discharge capacity STPH8-60

8.6 kW / 8 kW

10 kW / 8 kW

10 kW / 8 kW

Maximum charge / discharge capacity STPH10-60

8.6 kW / 8.6 kW

10 kW / 10 kW

10 kW / 10 kW

Maximum charge / discharge capacity STPH12-60

8.6 kW / 8.6 kW

11.5 kW / 11.5 kW

14.4 kW / 12 kW

Maximum charge / discharge capacity STPH15-60

8.6 kW / 8.6 kW

11.5 kW / 11.5 kW

14.4 kW / 14.4 kW

HVM+ 16.6

HVM+ 19.3

HVM+ 22.1

Voltage range of battery

240 V to 345 V

280 V to 403 V

320 V to 460 V

Maximum current

50 A

Maximum battery power

17.2 kW

20.1 kW

23 kW

Maximum charge / discharge capacity STPH5-60

10 kW / 5 kW

10 kW / 5 kW

10 kW / 5 kW

Maximum charge / discharge capacity STPH6-60

10 kW / 6 kW

10 kW / 6 kW

10 kW / 6 kW

Maximum charge / discharge capacity STPH8-60

10 kW / 8 kW

10 kW / 8 kW

10 kW / 8 kW

Maximum charge / discharge capacity STPH10-60

10 kW / 10 kW

10 kW / 10 kW

10 kW / 10 kW

Maximum charge / discharge capacity STPH12-60

15 kW / 12 kW

15 kW / 12 kW

15 kW / 12 kW

Maximum charge / discharge capacity STPH15-60

15 kW / 15 kW

15 kW / 15 kW

15 kW / 15 kW